How do ACT-1 actuator jam alarms work?

How do ACT-1 actuator jam alarms work?

If the jam alarm is disabled, the system essentially goes into a cycle of constantly turning on the relay in whatever direction it was going to attempt to reach the target position. The jam threshold is: If it takes longer than 20s to reach its position it’ll go into the paused jam state (when jam alarm is enable) or go into a retry cycle (when disabled).
 
What is the operation if the jam alarm is disabled. Would it turn off the relay if a jam occurred?
As described above, if the jam alarm is disabled, the relays will continue to close the curtain to try and reach 0%. The close relay will turn on for 20s at a time, take a few seconds break (like when switching directions) and then retry closing again, indefinitely.

What is the normal result of a jam alarm? Does it manually override it, or just go idle?
The ACT-1 goes into a state similar to IDLE, and not overridden. But override commands can be used to attempt to unjam the ACT, similar to an UNJAM. The UNJAM command itself also does the same as a retry loop (what happens when the alarm is disabled).
    • Related Articles

    • Setting up an Inlet / Actuator / Curtain WITH Feedback

      Setting up an actuator in AutoFlex Connect These instructions are for actuators that require a feedback signal and will be programmed for traditional staged ventilation. The two main steps are configuration and programming. Configuration 1. Go to the ...
    • Setting up an Inlet / Actuator / Curtain WITHOUT Feedback

      Setting up an actuator without feedback These instructions are for actuators that do not require a feedback signal and will be programmed for traditional staged ventilation. The two main steps are configuration and programming. Configuration 1. Go to ...
    • Actuator de-icing clarification

      Actuator deicing will move the actuators a certain distance and back to their position as per the settings every few hours in order to break up any potential ice build up on the inlets.
    • How do I calibrate my actuator?

      Push on the actuator widget, then the Gears icon for settings, then Calibrate Actuator.
    • Troubleshooting actuator potentiometer feedback wiring

      Troubleshooting actuator potentiometer feedback wiring The feedback potentiometer wiring must be properly connected to the control. Determining the correct wiring can be difficult on some actuators or potentiometers. Common symptoms of incorrect ...