Inlet / Actuator / Curtain
What is the hysteresis for actuators with feedback?
There is a hard-coded 1% hysteresis for ACT-1 controlled actuators with feedback.
What triggers an actuator jammed alarm?
When an actuator tries to move for 20 seconds and the ADC value does not change by at least 5 an actuator jammed alarm is triggered.
Can an ACT-1T control an inlet or curtain via a contactor?
No. The ACT-1T uses the current sensor during the calibration process. If the ACT-1T is connected to a contactor that is switching the motors on and off, then it is not getting the current from the load, and will not calibrate or operate properly. In ...
Can I control my winch without feedback?
Yes, the traditional timed-based curtain control can be used to control winches without feedback. You can use the ACT-1 or ACT-1T module.
Air curtain operation explained
Air curtain settings This is the status and physical order of the air curtain bags. The numbers correspond with blower numbers in item B. This is the list of blowers, in the order they inflate. The blower button that is selected is the one that you ...
Setting up an Inlet / Actuator / Curtain WITHOUT Feedback
Setting up an actuator without feedback These instructions are for actuators that do not require a feedback signal and will be programmed for traditional staged ventilation. The two main steps are configuration and programming. Configuration 1. Go to ...
Setting up an Inlet / Actuator / Curtain WITH Feedback
Setting up an actuator in AutoFlex Connect These instructions are for actuators that require a feedback signal and will be programmed for traditional staged ventilation. The two main steps are configuration and programming. Configuration 1. Go to the ...