Windspeed is reading much higher than actual on DOL58
Windspeed is reading much higher than actual on DOL58
If you are seeing consistently higher windspeed readings than expected, doublecheck your wiring. Having the windspeed and wind direction wires exchanged could cause this issue.
Do you have a minimum ventilation rate greater than 0% in your VentGrid settings? If you have your minimum ventilation higher than 0%, it will cause the VentGrid to add to the vent rate because the start of the VentGrid will be whatever value greater ...
Double check outdoor probe configuration. If the “Control” option for the outside temp probe is checked, this adds it in to the average with your other two probes.
Check if there are other temperature sensors assigned to control that equipment group. A temperature sensor in a different room or an outdoor sensor could be incorrectly assigned to control for that group and is being added into the averaging ...
If your Plus-Touch temperature reading is stuck on one single temperature you may have the temperature manually overridden. Go to the Menu, then Manual Override. Either hit Auto All to change all outputs and sensors back to automatic operation, or ...
If your Supra-Touch temperature reading is stuck on one single temperature you may have the temperature manually overridden. Go to the Menu, then Manual Override. Either hit Auto All to change all outputs and sensors back to automatic operation, or ...