Why did my room / configuration / settings disappear after I power cycled my control?

Why did my room / configuration / settings disappear after I power cycled my control?

If you have a new AutoFlex Connect that is losing configuration or settings when the control is power cycled, you may have left the battery isolation tab in place. This tab prevents the battery from discharging during shipping or when the control is off for long periods of time. It should not be in place when the control is in use, as any power cycle will result in a "hard" shut-down which can cause the operating system to behave strangely, like not saving configuration or settings that you had previously created.

The battery isolation tab can be found on the backside of the display on the single board computer.