Where do I connect the disconnect relay?

Where do I connect the disconnect relay?

Connect the disconnect relay to the Start/Stop connections on your equipment. See Connect equipment in the user manual for more information.
    • Related Articles

    • Can I use the disconnect relay to control a fan?

      No. The disconnect relay is designed to send a stop signal to the 0 to 10 VDC equipment it is controlling when the variable output goes to 0 V.
    • Can I do minimum ventilation duty cycles on the AutoFlex Connect?

      There is not a simple software way of doing this, but there is a way. Wire the output of the variable through a relay before it goes to the fan. (L1 goes to one VAR terminal, the second VAR terminal goes to the relay, and then the second relay ...
    • Why does my equipment still run when the output is at 0 percent?

      Some equipment may still operate at a very low value at 0 percent. Use the disconnect relay to fully cut off the power to the equipment and ensure that 0 percent means fully off. See Connect Equipment in the user manual for more information.
    • Relay not operating load

      Problem Relay not operating load Possible Cause Possible Solution Incorrect wiring Correct the wiring. Switch-on setting for stage incorrect Adjust the setting. Relay set to cool for a heater Relay set to heat for a fan No power to load Switch on the ...
    • Relay not operating load

      Problem Relay not operating load Possible Cause Possible Solution Incorrect wiring Correct the wiring. Switch-on setting for stage incorrect Adjust the setting. Relay set to cool for a heater Relay set to heat for a fan No power to load Switch on the ...