Where do I connect the disconnect relay?
Connect
the disconnect relay to the Start/Stop connections on your equipment. See Connect
equipment in the user manual for more information.
Related Articles
Can I use the disconnect relay to control a fan?
No. The disconnect relay is designed to send a stop signal to the 0 to 10 VDC equipment it is controlling when the variable output goes to 0 V.
Can I do minimum ventilation duty cycles on the AutoFlex Connect?
There is not a simple software way of doing this, but there is a way. Wire the output of the variable through a relay before it goes to the fan. (L1 goes to one VAR terminal, the second VAR terminal goes to the relay, and then the second relay ...
Why does my equipment still run when the output is at 0 percent?
Some equipment may still operate at a very low value at 0 percent. Use the disconnect relay to fully cut off the power to the equipment and ensure that 0 percent means fully off. See Connect Equipment in the user manual for more information.
Relay not operating load
Problem Relay not operating load Possible Cause Possible Solution Incorrect wiring Correct the wiring. Switch-on setting for stage incorrect Adjust the setting. Relay set to cool for a heater Relay set to heat for a fan No power to load Switch on the ...
Relay not operating load
Problem Relay not operating load Possible Cause Possible Solution Incorrect wiring Correct the wiring. Switch-on setting for stage incorrect Adjust the setting. Relay set to cool for a heater Relay set to heat for a fan No power to load Switch on the ...