What can I connect to the temperature or alarm terminals?
The
TEMP1, TEMP2, SENSOR1, and ALARM terminals are not used in the TEB-6. Do not
connect any equipment to these terminals.
Related Articles
Alarm Codes and Error Messages
ALARM MESSAGE POSSIBLE CAUSE POSSIBLE SOLUTION Power Fail Alarm There has been a power failure. Check to see why the power failed and then fix the problem. The temperature probe or sensor cable has short circuited. The temperature probe is damaged or ...
Does a low or high temperature alarm affect the output?
No. If there is a low or high temperature alarm the, alarm contacts will change state but the variable output will continue to operate according to the programmed settings.
Temperature does not change
Problem Temperature does not change Possible Cause Possible Solution There are no working temperature probes enabled or connected Make sure at least one working probe is enabled. The control is in temperature test mode. If the TEST LED is on, the ...
Temperature does not change
Problem Temperature does not change Possible Cause Possible Solution There are no working temperature probes enabled or connected Make sure at least one working probe is enabled. The control is in temperature test mode. If the TEST LED is on, the ...
Alarm Codes and Error Messages
ALARM MESSAGE POSSIBLE CAUSE POSSIBLE SOLUTION High Temperature Alarm The temperature has gone above the high temperature alarm point. Try to lower the temperature by turning heaters down or off, or by increasing or turning on cooling elements (such ...