Staged heater cycles on and off

Staged heater cycles on and off

Problem
Staged heater cycles on and off

Possible Cause
Possible Solution
The heater set points are too close together with variable speed fans.
  1. Adjust the hysteresis setting.
  2. Move the temperature probe closer to the heater.
  3. Widen the set points.
The heater is too large for the room
Replace the heater with a smaller output unit.
The stage is set up as a duty cycle
Remove the duty cycle from the stage’s settings


    • Related Articles

    • Staged heater cycles on and off

      Problem Staged heater cycles on and off Possible Cause Possible Solution Heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. Heater ...
    • Staged heater cycles on and off

      Problem Staged heater cycles on and off Possible Cause Possible Solution The heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. The ...
    • Staged heater cycles on and off

      Problem Staged heater cycles on and off Possible Cause Possible Solution The heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. The ...
    • Staged heater cycles on and off

      Problem Staged heater cycles on and off Possible Cause Possible Solution Heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. Heater ...
    • Staged heater cycles on and off

      Problem Staged heater cycles on and off Possible Cause Possible Solution Heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. Heater ...