Staged heater cycles on and off
Problem
Staged heater cycles on and
off
Possible Cause | Possible Solution |
Heater set points are too
close together with variable speed fans. | - Adjust the hysteresis setting.
- Move the temperature probe closer to the heater.
- Widen the set points.
|
Heater too large for room | Replace the heater with a
smaller output unit. |
Stage is set up as a
temperature-based duty cycle | Remove the duty cycle from
the stage’s settings. |
Related Articles
Staged heater cycles on and off
Problem Staged heater cycles on and off Possible Cause Possible Solution Heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. Heater ...
Staged heater cycles on and off
Problem Staged heater cycles on and off Possible Cause Possible Solution The heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. The ...
Staged heater cycles on and off
Problem Staged heater cycles on and off Possible Cause Possible Solution The heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. The ...
Staged heater cycles on and off
Problem Staged heater cycles on and off Possible Cause Possible Solution The heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. The ...
Staged heater cycles on and off
Problem Staged heater cycles on and off Possible Cause Possible Solution Heater set points are too close together with variable speed fans. Adjust the hysteresis setting. Move the temperature probe closer to the heater. Widen the set points. Heater ...