How many VFDs can the FC-1T-1VDC control?

How many VFDs can the FC-1T-1VDC control?

The output rating is 2k Ω of load. Each device or wire attached to the output adds to the load. The total number of VFDs it can control depends on the VFDs and well as the length of wiring connecting them.
    • Related Articles

    • Controlling 0 - 10 volt dc lighting with the VDC-4

      This article is for general information. Always refer to local electrical codes for acceptable installations. This article addresses 0-10 volt dc controlled light fixtures. While the main focus will be on LED lighting, the information could be ...
    • How many fans can the FC-1T-1VAC control?

      The limiting factor is the variable stage rating. Add up the current draw of the fans you want to control and compare it to the variable stage rating. If the combined fans draw less than the variable stage rating then you can control them.
    • How many lights can the LDB control?

      It depends on the maximum current that the lights will draw. Refer to the technical specifications of the lights to find the maximum current draw. Divide the LDB’s variable stage rating by the maximum draw of the lights to determine how many of them ...
    • Can the FC-1T-1VAC-1F control fixed speed fans?

      No, the fixed stage is for a heater only. The FC-1T-1F controls fixed-speed fans.
    • How many fans can it control?

      The limiting factor is the variable stage rating. Add up the current draw of the fans you want to control and compare it to the variable stage rating. If the combined fans draw less than the variable stage rating, then you can control them.