Can the AutoFlex Connect-2 control heat lamps?

Can the AutoFlex Connect-2 control heat lamps?

To control heat lamps within the AutoFlex Connect-2 you would use a VAC-1 board.  https://phason.ca/pdfs/vac-1.pdf

  

Heat lamps can be controlled via a VAC-1 module, assigning the output as “Variable Heating”.

 

Once you have the module configured, the settings will work like a variable cooling fan, but in the opposite direction.




 Minimum Load: This is the % output where the heat lamps start. (kind of like Idle Speed) In the example above, the 20 represents % of heat.

Heat Cut off: This is the Temperature at which the Heat Lamps will shut off completely. In the image above the Heat Cutoff  is set at 17C.
Set Point: As the Temperature reading falls and hit’s the “Set Point”, the output % will begin to proportionally increase. In the image above the Set Point is set at 15C.

Differential: This is the Temperature reading at which the Heat Lamps will be at 100%. In the image above the Set Point is set at 9C.

 

We can’t directly control based on Wattage, however if the electrician measured the wattage, he may be able to use his measurements to adjust the settings and achieve something similar.

 

Also the VAC-1 module is rated for a maximum load of 800W @ 120V / 1600 W @ 230V. Anything beyond that will require a VLX-20 slave box  https://phason.ca/variable-load-expansion.htm