Group reading is higher than the average of 2 probes
Group reading is higher than the average of 2 probes
Double check outdoor probe configuration. If the “Control” option for the outside temp probe is checked, this adds it in to the average with your other two probes.
Check if there are other temperature sensors assigned to control that equipment group. A temperature sensor in a different room or an outdoor sensor could be incorrectly assigned to control for that group and is being added into the averaging ...
If you are seeing consistently higher windspeed readings than expected, doublecheck your wiring. Having the windspeed and wind direction wires exchanged could cause this issue.
Do you have a minimum ventilation rate greater than 0% in your VentGrid settings? If you have your minimum ventilation higher than 0%, it will cause the VentGrid to add to the vent rate because the start of the VentGrid will be whatever value greater ...
Question: With the AST, you can’t change the % of base weight like the ASC, it’s determined off the lowest weight group start weight (65%). When you switch to HUI mode, does it stay based off the lowest weight group number in your auto sort settings, ...