Can a current sense input be paired to an output?
Yes, a CurrentSense-2 can be configured to an IN-4 input. That input can then be assigned to an RM-4 output. This allows for a high alarm shut-off to be enabled for that output, similar to what an RM-2 is capable of.
Related Articles
Does the LB White Smart Sense heating work with the AFX?
Yes, the AutoFlex Connect can control a LB White Smart Sense heater, it will use (1) variable DC output. Setup as Variable Heating. Note: The modulating control valve does not open until 5V dc. Keep this in mind when programming controls for use with ...
Does a low or high temperature alarm affect the output?
No. If there is a low or high temperature alarm the, alarm contacts will change state but the variable output will continue to operate according to the programmed settings.
Why do I measure full voltage output when the control says it should be less?
The control and expansions need to have a load connected for the triac to give a correct output. If there are no mats (load) connected to the triac output, the output will always read full voltage, no matter what you set the control to. As soon as ...
Output is stuck at 100%
1. Verify phasing and field wiring 2. Verify slave A to B wiring 3. Remove VAR load wire from VLX-20. Measure this to ground, and see if it has no voltage or if there is somewhere further on that circuit that is sourcing voltage to load. If there is ...
Does the AutoFlex Connect have a manual override?
Yes. There is a software manual override that can be accessed from each input or output's menu.